Arester kilat polimer 35kV
35kV
Arrester Surge Seng-Oksida
Umume
Arrester Surge Tipe Seng Oksida minangka protektor voltase maju paling anyar kanggo jalur distribusi lan piranti stasiun listrik. Digabungake karo seng oksida lan oksida logam liyane minangka disk resistor inti, karakteristik volt-ampere lan kemampuan resisten resistor resisten saiki meningkat kanthi drastis dibandhingake karo arrester lonjakan jinis SiC konvensional.
Ing voltase operasi nominal, arus liwat arrester surge mung kira-kira kelas mikro-ampere. Nalika arrester lonjakan ngalami voltase sing gedhe, disk resistor kanthi karakteristik non-linier sing apik bakal nambah arus liwat arrester lonjakan nganti pirang-pirang ewu ampere kanthi cepet. Arrester surge ana ing negara sing lagi nindakake lan banjur bakal ngeculake energi sing kakehan voltase menyang bumi lan nglindhungi piranti transmisi distribusi daya I saka pengaruh voltase luwih saka.
Arrester Surge Seng-Oksida Parameter Teknis Key |
|||||||
Arus debit nominal: 5KA |
|||||||
Jinis MOA |
MOA Dirating |
MCOV |
1 / 10µ impuls saiki tajem |
8 / 20µ impuls saiki |
30 / 60µs ngoper impuls saiki |
2ms impuls saiki persegi dowo |
4 / 10µ impuls saiki sing dhuwur |
kV (rms) |
KV |
A |
kA |
||||
YH5W-3 |
3 |
2,55 |
11.3 |
9 |
8,90 |
150 |
65 |
YH5W-6 |
6 |
5.10 |
22.6 |
18 |
16.8 |
150 |
65 |
YH5W-9 |
9 |
7.65 |
33.7 |
27 |
23.8 |
150 |
65 |
YH5W-10 |
10 |
8.40 |
36.0 |
30 |
26.4 |
150 |
65 |
YH5W-1 才 |
11 |
9.40 |
40.0 |
33 |
30.0 |
150 |
65 |
YH5W-12 |
12 |
10.2 |
42.2 |
36 |
31.7 |
150 |
65 |
YH5W-15 |
15 |
12.7 |
51.0 |
45 |
38.5 |
150 |
65 |
YH5W-18 |
18 |
15.3 |
61.5 |
54 |
46.5 |
150 |
65 |
YH5W-21 |
21 |
17.0 |
71.8 |
63 |
54.5 |
150 |
65 |
YH5W-24 |
24 |
19.5 |
82.0 |
72 |
62.6 |
150 |
65 |
YH5W-27 |
27 |
22.0 |
92.0 |
81 |
69.8 |
150 |
65 |
YH5W-30 |
30 |
24.4 |
102 |
90 |
79.0 |
150 |
65 |
YH5W-33 |
33 |
27.5 |
112 |
99 |
86.7 |
150 |
65 |
YH5W-36 |
36 |
29.0 |
117 |
103 |
92.4 |
150 |
65 |
YH5W-39 |
39 |
31.5 |
123 |
108 |
94.0 |
150 |
65 |
YH5W-42 |
42 |
34.0 |
126 |
111 |
101 |
150 |
65 |
YH5W-45 |
45 |
36.5 |
128 |
119 |
105 |
150 |
65 |
YH5W-48 |
48 |
39.0 |
139 |
127 |
110 |
150 |
65 |
YH5W-51 |
51 |
40.8 |
151 |
134 |
115 |
150 |
65 |
YH5W-54 |
54 |
42.0 |
160 |
143 |
119 |
150 |
65 |
YH5W-60 |
60 |
48.0 |
178 |
159 |
132 |
150 |
65 |
YH5W-66 |
66 |
53.0 |
196 |
175 |
145 |
150 |
65 |
YH5W-69 |
69 |
55.2 |
205 |
183 |
152 |
150 |
65 |
Parameter Teknis Tombol Perumahan Polimerik Surge (Kilat) Arrester | |||||||
Arus debit nominal: 10KA |
|||||||
Jinis MOA |
MOA Dirating |
MCOV |
1 / 10µ impuls saiki tajem |
8 / 20µ impuls saiki |
30 / 60µs ngoper impuls saiki |
2ms impuls saiki persegi dowo |
4 / 10µ impuls saiki sing dhuwur |
kV (rms) |
KV |
A |
kA |
||||
YH10W-3 |
3 |
2,55 |
10.3 |
8.40 |
7.70 |
250 |
100 |
YH10W-6 |
6 |
5.10 |
20.5 |
16.7 |
15.4 |
250 |
100 |
YH10W-9 |
9 |
7.65 |
31.0 |
25.0 |
23.1 |
250 |
100 |
YH10W-10 |
10 |
8.40 |
33.0 |
27.4 |
27.0 |
250 |
100 |
YH10W-11 |
11 |
9.40 |
36.4 |
30.4 |
30.0 |
250 |
100 |
YH10W-12 |
12 |
10.2 |
38.5 |
33.3 |
30.8 |
250 |
100 |
YH10W-15 |
15 |
12.7 |
46.5 |
41.4 |
38.5 |
250 |
100 |
YH10W-18 |
18 |
15.3 |
56.0 |
49.8 |
46.2 |
250 |
100 |
YH10W-21 |
21 |
17.0 |
65.5 |
57.0 |
53.9 |
250 |
100 |
YH10W-24 |
24 |
19.5 |
75.0 |
65.0 |
61.6 |
250 |
100 |
YH10W-27 |
27 |
22.0 |
84.0 |
74.0 |
69.3 |
250 |
100 |
YH10W-30 |
30 |
24.4 |
93.0 |
82.0 |
76.5 |
250 |
100 |
YH10W-33 |
33 |
27.5 |
101 |
90.0 |
84.7 |
250 |
100 |
YH10W-36 |
36 |
29.0 |
112 |
98.0 |
92.4 |
250 |
100 |
YH10W-39 |
39 |
31.5 |
117 |
103 |
94.0 |
250 |
100 |
YH10W-42 |
42 |
34.0 |
126 |
111 |
101 |
250 |
100 |
YH10W-45 |
45 |
36.5 |
128 |
119 |
105 |
250 |
100 |
YH10W-48 |
48 |
39.0 |
139 |
127 |
110 |
250 |
100 |
YH10W-51 |
51 |
40.8 |
151 |
134 |
115 |
250 |
100 |
YH10W-54 |
54 |
42.0 |
160 |
143 |
119 |
250 |
100 |
YH10W-60 |
60 |
48.0 |
178 |
159 |
132 |
400 |
100 |
YH10W-66 |
66 |
53.0 |
196 |
175 |
145 |
400 |
100 |
YH10W-69 |
49 |
55.2 |
205 |
183 |
152 |
400 |
100 |
YH10W-72 |
72 |
57.0 |
214 |
191 |
158 |
400 |
100 |
YH10W-75 |
75 |
60.0 |
223 |
199 |
165 |
400 |
100 |
YH10W-84 |
84 |
68.0 |
244 |
218 |
181 |
600 |
100 |
YH10W-90 |
90 |
70.0 |
249 |
234 |
184 |
600 |
100 |
YH10W-96 |
96 |
76.0 |
265 |
247 |
201 |
600 |
100 |
YH10W-108 |
108 |
84.0 |
298 |
273 |
222 |
600 |
100 |
YH10W-120 |
120 |
98.0 |
338 |
319 |
259 |
600 |
100 |
YH10W-132 |
132 |
106 |
367 |
345 |
280 |
600 |
100 |
YH10W-144 |
144 |
115 |
397 |
374 |
304 |
600 |
100 |
YH10W-168 |
168 |
131 |
452 |
426 |
346 |
600 |
100 |
YH10W-172 |
172 |
140 |
483 |
455 |
370 |
600 |
100 |
YH10W-180 |
180 |
144 |
497 |
468 |
380 |
600 |
100 |