6kV
Seng-OksidaPenahan Lonjakan
Jenderal
Lonjakan Tipe Seng OksidaPenangkapminangka pelindung tegangan luwih canggih paling anyar kanggo jalur distribusi lan piranti pembangkit listrik. Digabungake karo seng oksida lan oksida logam liyane minangka cakram resistor inti, karakteristik volt-ampere lan kemampuan arus liwat saka resistor discare saya apik banget dibandhingake karo arrester surge tipe SiC konvensional.
Ing voltase operasi nominal, arus sing liwat surge arrester mung kira-kira tingkat mikro-ampere. Nalika surge arrester ngalami over-voltage, cakram resistor kanthi karakteristik non-linier sing apik banget bakal nambah arus sing liwat surge arrester dadi pirang-pirang ewu ampere kanthi cepet. Surge arrester ana ing kahanan konduksi lan banjur bakal ngeculake energi over-voltage menyang bumi lan kanthi mangkono nglindhungi piranti transmisi distribusi daya I saka dampak over-voltage.
| Penahan Lonjakan Seng-Oksida Parameter Teknis Utama | |||||||
| Arus debit nominal: 5KA | |||||||
| Tipe MOA | Dirating MOA | MCOV | Impuls arus tajem 1/10µs | Impuls arus kilat 8/20µs | Impuls arus saklar 30/60µs | Tahanan impuls arus persegi panjang 2ms | Tahan impuls arus dhuwur 4/10µs |
| kV (rms) | ≮kV | A | kA | ||||
| YH5W-3 | 3 | 2.55 | 11.3 | 9 | 8.90 | 150 | 65 |
| YH5W-6 | 6 | 5.10 | 22.6 | 18 | 16.8 | 150 | 65 |
| YH5W-9 | 9 | 7.65 | 33.7 | 27 | 23.8 | 150 | 65 |
| YH5W-10 | 10 | 8.40 | 36.0 | 30 | 26.4 | 150 | 65 |
| YH5W-1 才 | 11 | 9.40 | 40.0 | 33 | 30.0 | 150 | 65 |
| YH5W-12 | 12 | 10.2 | 42.2 | 36 | 31.7 | 150 | 65 |
| YH5W-15 | 15 | 12.7 | 51.0 | 45 | 38.5 | 150 | 65 |
| YH5W-18 | 18 | 15.3 | 61.5 | 54 | 46.5 | 150 | 65 |
| YH5W-21 | 21 | 17.0 | 71.8 | 63 | 54.5 | 150 | 65 |
| YH5W-24 | 24 | 19.5 | 82.0 | 72 | 62.6 | 150 | 65 |
| YH5W-27 | 27 | 22.0 | 92.0 | 81 | 69.8 | 150 | 65 |
| YH5W-30 | 30 | 24.4 | 102 | 90 | 79.0 | 150 | 65 |
| YH5W-33 | 33 | 27.5 | 112 | 99 | 86.7 | 150 | 65 |
| YH5W-36 | 36 | 29.0 | 117 | 103 | 92.4 | 150 | 65 |
| YH5W-39 | 39 | 31.5 | 123 | 108 | 94.0 | 150 | 65 |
| YH5W-42 | 42 | 34.0 | 126 | 111 | 101 | 150 | 65 |
| YH5W-45 | 45 | 36.5 | 128 | 119 | 105 | 150 | 65 |
| YH5W-48 | 48 | 39.0 | 139 | 127 | 110 | 150 | 65 |
| YH5W-51 | 51 | 40.8 | 151 | 134 | 115 | 150 | 65 |
| YH5W-54 | 54 | 42.0 | 160 | 143 | 119 | 150 | 65 |
| YH5W-60 | 60 | 48.0 | 178 | 159 | 132 | 150 | 65 |
| YH5W-66 | 66 | 53.0 | 196 | 175 | 145 | 150 | 65 |
| YH5W-69 | 69 | 55.2 | 205 | 183 | 152 | 150 | 65 |
| Parameter Teknis Utama Perumahan Polimer Penangkal Lonjakan (Petir) | |||||||
| Arus debit nominal: 10KA | |||||||
| Tipe MOA | Dirating MOA | MCOV | Impuls arus tajem 1/10µs | Impuls arus kilat 8/20µs | Impuls arus saklar 30/60µs | Tahanan impuls arus persegi panjang 2ms | Tahan impuls arus dhuwur 4/10µs |
| kV (rms) | ≮kV | A | kA | ||||
| YH10W-3 | 3 | 2.55 | 10.3 | 8.40 | 7.70 | 250 | 100 |
| YH10W-6 | 6 | 5.10 | 20.5 | 16.7 | 15.4 | 250 | 100 |
| YH10W-9 | 9 | 7.65 | 31.0 | 25.0 | 23.1 | 250 | 100 |
| YH10W-10 | 10 | 8.40 | 33.0 | 27.4 | 27.0 | 250 | 100 |
| YH10W-11 | 11 | 9.40 | 36.4 | 30.4 | 30.0 | 250 | 100 |
| YH10W-12 | 12 | 10.2 | 38.5 | 33.3 | 30.8 | 250 | 100 |
| YH10W-15 | 15 | 12.7 | 46.5 | 41.4 | 38.5 | 250 | 100 |
| YH10W-18 | 18 | 15.3 | 56.0 | 49.8 | 46.2 | 250 | 100 |
| YH10W-21 | 21 | 17.0 | 65.5 | 57.0 | 53.9 | 250 | 100 |
| YH10W-24 | 24 | 19.5 | 75.0 | 65.0 | 61.6 | 250 | 100 |
| YH10W-27 | 27 | 22.0 | 84.0 | 74.0 | 69.3 | 250 | 100 |
| YH10W-30 | 30 | 24.4 | 93.0 | 82.0 | 76.5 | 250 | 100 |
| YH10W-33 | 33 | 27.5 | 101 | 90.0 | 84.7 | 250 | 100 |
| YH10W-36 | 36 | 29.0 | 112 | 98.0 | 92.4 | 250 | 100 |
| YH10W-39 | 39 | 31.5 | 117 | 103 | 94.0 | 250 | 100 |
| YH10W-42 | 42 | 34.0 | 126 | 111 | 101 | 250 | 100 |
| YH10W-45 | 45 | 36.5 | 128 | 119 | 105 | 250 | 100 |
| YH10W-48 | 48 | 39.0 | 139 | 127 | 110 | 250 | 100 |
| YH10W-51 | 51 | 40.8 | 151 | 134 | 115 | 250 | 100 |
| YH10W-54 | 54 | 42.0 | 160 | 143 | 119 | 250 | 100 |
| YH10W-60 | 60 | 48.0 | 178 | 159 | 132 | 400 | 100 |
| YH10W-66 | 66 | 53.0 | 196 | 175 | 145 | 400 | 100 |
| YH10W-69 | 49 | 55.2 | 205 | 183 | 152 | 400 | 100 |
| YH10W-72 | 72 | 57.0 | 214 | 191 | 158 | 400 | 100 |
| YH10W-75 | 75 | 60.0 | 223 | 199 | 165 | 400 | 100 |
| YH10W-84 | 84 | 68.0 | 244 | 218 | 181 | 600 | 100 |
| YH10W-90 | 90 | 70.0 | 249 | 234 | 184 | 600 | 100 |
| YH10W-96 | 96 | 76.0 | 265 | 247 | 201 | 600 | 100 |
| YH10W-108 | 108 | 84.0 | 298 | 273 | 222 | 600 | 100 |
| YH10W-120 | 120 | 98.0 | 338 | 319 | 259 | 600 | 100 |
| YH10W-132 | 132 | 106 | 367 | 345 | 280 | 600 | 100 |
| YH10W-144 | 144 | 115 | 397 | 374 | 304 | 600 | 100 |
| YH10W-168 | 168 | 131 | 452 | 426 | 346 | 600 | 100 |
| YH10W-172 | 172 | 140 | 483 | 455 | 370 | 600 | 100 |
| YH10W-180 | 180 | 144 | 497 | 468 | 380 | 600 | 100 |